ARBIS · Knowledge base

Knowledge base: how VRF and ventilation work

Operating principles, brand comparison, step-by-step VRF installation and documentation for designers.

01 · Operating principle

How a VRF system works

VRF (Variable Refrigerant Flow) is a system with variable refrigerant flow. One outdoor unit with an inverter compressor is connected by copper pipes to dozens of indoor units. Each indoor unit opens its electronic expansion valve (EEV) exactly as much as the room needs cooling or heating. The compressor adjusts its speed to the total load — without starts and stops — so the system is more economical than a set of ordinary splits.

Outdoor unit inverter compressor gas line liquid line refnet Cassette unit Ducted unit Wall-mounted unit EEV · 22 °CEEV · 24 °CEEV · off One pair of pipes for the whole building · individual temperature in every room · central controller and BMS integration
Heat pump

The whole system works either in cooling or in heating.

Heat recovery

Some rooms are cooled while others are heated at the same time.

Mini VRF

For cottages and small offices, single-phase power.

02 · Technical specifications

VRF lineup comparison

Brand / seriesOutdoor moduleMax. systemOperating rangeRefrigerant
MDV V8 (MDV8)8–40 HP120 HPcooling −15…+55 °C, heating −30…+30 °CR410A
MDV V8 Mini8–18 kW—for small buildingsR410A / R32
LG MULTI V i8–26 HP96 HP (4 units)cooling up to +52 °C, 22.4–268.8 kWR410A
AUX ARV VI25.2–61.5 kW (15 modules)24–402 kW−25…+52 °C; piping up to 1000 m, height difference up to 110 mR410A
AUX ARV mini10–26 kWup to 246.4 kWfor cottages and officesR410A
eco° PRO Modular VRF25.2–90 kWmodularcooling −5…+55 °C, heating −30…+30 °C; T3, Hitachi compressorR410A

Data from manufacturers' catalogues; before purchase we check against the current model specification.

03 · Guide

VRF system installation: 8 steps

Our team: design engineers, experienced site managers and certified installation crews. Complex routes — facades, shafts, heights: insulated ducts, fans and exhaust mains are assembled with the building's architecture in mind.

ARBIS crew work sequence. Exact lengths, height differences and pressures — per the manufacturer's manual for the specific model.

01
Calculation and selection

Heat gains per room, selection of indoor units and outdoor module, check of the connection ratio.

02
Piping and refnet layout

Pipe diameters, allowable lengths and height differences — per manufacturer tables; refnets from the brand's kit.

03
Indoor units and drainage

Suspension on threaded rods with vibration isolation, drainage with at least 1% slope, traps where needed.

04
Copper piping

Brazing with nitrogen purge, no scale; insulation of every pipe; supports at code-specified spacing.

05
Nitrogen pressure test

At the pressure specified by the manufacturer (for R410A usually 4.0 MPa), with holding time and record in the report.

06
Evacuation

With a two-stage pump to deep vacuum, hold check.

07
Refrigerant top-up

Amount — by length and diameter of liquid lines, weighed on scales.

08
Wiring, addressing, commissioning

Communication line between units, unit addressing, test run, report and staff training.

04 · Ventilation

How an air handling unit works

Damper Filter Heat recovery Heater Cooler Fan

Outside air passes through the damper and filter, picks up heat from exhaust air in the heat exchanger, is heated or cooled to the required temperature and supplied by the fan through ducts to the rooms. This is how our КЦКП AHUs and compact units work.

VRF instead of a chiller. The cooling/heating coil of a КЦКП AHU can be fed from a VRF outdoor unit via the MDV AHU Kit (AHUKZ-00F…04F, 1.8 to 168 kW) — one system for air conditioning and supply ventilation.
05 · Equipment

We supply and install

06 · Documents

Catalogues, manuals and Revit families

MDV AHU Kit AHUKZ-00F…04F — installation and operation manualRequest on Telegram MDV AHU Kit — service manualRequest on Telegram MDV AHU Kit — Revit family for designersRFA ↓ AUX 2025 — professional climate systems catalogueRequest on Telegram AUX light-commercial R32 — service manualRequest on Telegram AUX — operation and installation manualRequest on Telegram AUX — refrigerant top-up and piping length tablePDF ↓ ARBIS KLIMAT SERVIS — products and services catalogueRequest on Telegram

Questions about selection or installation?

An ARBIS engineer will reply in the messenger during working hours.

Address: Tashkent, Mirabad district, A. Fitrat St., 180V — entrance through the «VERANO» arch
Phone: +998 99 831 11 74 · Mon–Fri 08:00–18:00
Email: arbisklimatservis@gmail.com

Telegram — @Arbisklimatservis WhatsApp — +998 99 831 11 74